Backflow assembly test: 505 Hickory Dr
ApprovedFiled Jan 14, 2026 by Avery Ramirez, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Jan 14, 2026
- Assembly type
- DC
- Serial number
- B995176
- Size
- 3/4
- Test gauge serial
- G-7582
- Gauge calibration date
- Jan 16, 2025
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ramirez, current on the service date
- All required fields present
- Address matches parcel 051-32-01227
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
505 Hickory Dr
Owner: Riley Whitcomb
Parcel 051-32-01227