Backflow assembly test: Golden Market

Approved

Filed Nov 1, 2023 by Avery Ramirez, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Nov 1, 2023
Assembly type
RP
Serial number
K623323
Size
2
Test gauge serial
G-2711
Gauge calibration date
Sep 3, 2023
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 051-69-01269
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.