Backflow assembly test: Golden Market

Approved

Filed Oct 31, 2024 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 31, 2024
Assembly type
RP
Serial number
K623323
Size
2
Test gauge serial
G-8127
Gauge calibration date
Oct 12, 2023
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-69-01269
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.