Back to the backflow review queue
Backflow assembly test: 5039 Laurel Trl
Needs reviewFiled Nov 17, 2026 by Shawn Nguyen, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Nov 17, 2026
- Assembly type
- RP
- Serial number
- W672935
- Size
- 1
- Test gauge serial
- G-3585
- Gauge calibration date
- May 26, 2026
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-47-01129
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
5039 Laurel Trl
Owner: Avery Wexler
Parcel 051-47-01129