Back to the backflow review queue
Backflow assembly test: Crossroads Car Wash
ApprovedFiled Sep 15, 2024 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 15, 2024
- Assembly type
- RP
- Serial number
- K793594
- Size
- 4
- Test gauge serial
- G-6927
- Gauge calibration date
- Dec 27, 2023
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-17-01053
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7928 Mill Creek Trl
Owner: Benton Holdings LLC
Parcel 051-17-01053