Back to the backflow review queue

Backflow assembly test: Crossroads Car Wash

Approved

Filed Sep 15, 2024 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Sep 15, 2024
Assembly type
RP
Serial number
K793594
Size
4
Test gauge serial
G-6927
Gauge calibration date
Dec 27, 2023
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-17-01053
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7928 Mill Creek Trl
Owner: Benton Holdings LLC
Parcel 051-17-01053