Back to the backflow review queue
Backflow assembly test: Crossroads Car Wash
ApprovedFiled Aug 27, 2025 by Avery Ramirez, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 27, 2025
- Assembly type
- RP
- Serial number
- K793594
- Size
- 4
- Test gauge serial
- G-7448
- Gauge calibration date
- Jun 30, 2025
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Ramirez, current on the service date
- All required fields present
- Address matches parcel 051-17-01053
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7928 Mill Creek Trl
Owner: Benton Holdings LLC
Parcel 051-17-01053