Backflow assembly test: Golden Taqueria

Approved

Filed Jul 8, 2025 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 8, 2025
Assembly type
RP
Serial number
B741051
Size
2
Test gauge serial
G-9772
Gauge calibration date
May 10, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-95-01115
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8225 Sycamore Trl
Owner: Ramirez Holdings LLC
Parcel 051-95-01115