Backflow assembly test: Maple Leaf Apartments

Approved

Filed Oct 9, 2024 by Avery Ramirez, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Oct 9, 2024
Assembly type
RP
Serial number
Z473358
Size
1
Test gauge serial
G-7109
Gauge calibration date
Apr 15, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 051-97-01153
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8458 Mill Creek Trl
Owner: Fairley Holdings LLC
Parcel 051-97-01153