Backflow assembly test: Two Rivers Animal Hospital
ApprovedFiled Nov 13, 2025 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 13, 2025
- Assembly type
- DC
- Serial number
- A541517
- Size
- 2
- Test gauge serial
- G-8034
- Gauge calibration date
- Jul 9, 2025
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-62-01299
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4357 Sycamore Dr
Owner: Stroud Holdings LLC
Parcel 051-62-01299