Back to the backflow review queue

Backflow assembly test: Riverside Bakery

Approved

Filed Dec 14, 2025 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 14, 2025
Assembly type
RP
Serial number
W881981
Size
2
Test gauge serial
G-4077
Gauge calibration date
Aug 14, 2025
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-71-01181
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1442 Old Church Ln
Owner: Pruitt Holdings LLC
Parcel 051-71-01181