Backflow assembly test: Main Street Elementary School
ApprovedFiled Aug 3, 2026 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 3, 2026
- Assembly type
- RP
- Serial number
- K151821
- Size
- 2
- Test gauge serial
- G-1197
- Gauge calibration date
- Jun 29, 2026
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-39-01232
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.