Backflow assembly test: Corner Car Wash

Approved

Filed Oct 13, 2025 by Avery Ramirez, Heritage Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 13, 2025
Assembly type
RP
Serial number
Z346803
Size
1
Test gauge serial
G-4633
Gauge calibration date
Feb 15, 2025
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 051-62-01309
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8182 Stone Gate Ln
Owner: Brandt Holdings LLC
Parcel 051-62-01309