Backflow assembly test: Hilltop Elementary School

Approved

Filed Jul 29, 2024 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Jul 29, 2024
Assembly type
RP
Serial number
B994711
Size
1
Test gauge serial
G-7501
Gauge calibration date
May 27, 2024
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-35-01297
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.