Backflow assembly test: Hilltop Elementary School
ApprovedFiled Aug 13, 2025 by Shawn Nguyen, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 13, 2025
- Assembly type
- RP
- Serial number
- B994711
- Size
- 1
- Test gauge serial
- G-6899
- Gauge calibration date
- Dec 13, 2024
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-35-01297
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.