Backflow assembly test: 2230 Spring Branch Dr

Approved

Filed Dec 25, 2024 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 25, 2024
Assembly type
RP
Serial number
W983960
Size
3/4
Test gauge serial
G-1329
Gauge calibration date
Mar 10, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-22-01030
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.