Backflow assembly test: 2230 Spring Branch Dr

Approved

Filed Jan 18, 2026 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 18, 2026
Assembly type
RP
Serial number
W983960
Size
3/4
Test gauge serial
G-3851
Gauge calibration date
Aug 12, 2025
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-22-01030
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2230 Spring Branch Dr
Owner: Emerson Harlow
Parcel 051-22-01030