Back to the backflow review queue

Backflow assembly test: Maple Leaf Car Wash

Approved

Filed Nov 6, 2026 by Avery Ramirez, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Nov 6, 2026
Assembly type
RP
Serial number
Z139267
Size
1
Test gauge serial
G-6313
Gauge calibration date
Apr 11, 2026
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 051-60-01286
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9721 Quarry Rd
Owner: Lindqvist Holdings LLC
Parcel 051-60-01286