Back to the backflow review queue

Backflow assembly test: 5707 Hickory Ct

Approved

Filed Dec 19, 2023 by Cameron Kessler, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 19, 2023
Assembly type
RP
Serial number
W269991
Size
1
Test gauge serial
G-4579
Gauge calibration date
Jul 27, 2023
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-27-01100
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5707 Hickory Ct
Owner: Parker Okafor
Parcel 053-27-01100