Back to the backflow review queue

Backflow assembly test: 4964 Sycamore Way

Approved

Filed Dec 3, 2024 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 3, 2024
Assembly type
RP
Serial number
Z301580
Size
1
Test gauge serial
G-7607
Gauge calibration date
May 28, 2024
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 053-84-01123
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4964 Sycamore Way
Owner: Alex Fairley
Parcel 053-84-01123