Back to the backflow review queue
Backflow assembly test: 4964 Sycamore Way
ApprovedFiled Dec 3, 2024 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 3, 2024
- Assembly type
- RP
- Serial number
- Z301580
- Size
- 1
- Test gauge serial
- G-7607
- Gauge calibration date
- May 28, 2024
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Pruitt, current on the service date
- All required fields present
- Address matches parcel 053-84-01123
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4964 Sycamore Way
Owner: Alex Fairley
Parcel 053-84-01123