Back to the backflow review queue

Backflow assembly test: Riverside Pizza

Approved

Filed Jul 18, 2023 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 18, 2023
Assembly type
RP
Serial number
Z625323
Size
1 1/2
Test gauge serial
G-8147
Gauge calibration date
Oct 28, 2022
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-77-01286
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6315 Quarry Way
Owner: Pruitt Holdings LLC
Parcel 053-77-01286