Back to the backflow review queue

Backflow assembly test: 3226 Hickory Ln

Approved

Filed Aug 28, 2026 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 28, 2026
Assembly type
RP
Serial number
W771314
Size
1
Test gauge serial
G-6216
Gauge calibration date
Nov 1, 2025
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-29-01124
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3226 Hickory Ln
Owner: Morgan Wexler
Parcel 053-29-01124