Back to the backflow review queue

Backflow assembly test: Crossroads Animal Hospital

Approved

Filed Nov 29, 2023 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 29, 2023
Assembly type
RP
Serial number
A162691
Size
1 1/2
Test gauge serial
G-8203
Gauge calibration date
Oct 27, 2023
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Hollins, current on the service date
  • All required fields present
  • Address matches parcel 053-71-01267
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7983 Laurel Rd
Owner: Ramirez Holdings LLC
Parcel 053-71-01267