Backflow assembly test: 1460 Hickory Ct

Approved

Filed Dec 11, 2025 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 11, 2025
Assembly type
RP
Serial number
W333234
Size
3/4
Test gauge serial
G-4068
Gauge calibration date
Oct 5, 2025
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
3.8 psid
Relief valve opened at
3.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 053-20-01109
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1460 Hickory Ct
Owner: Cameron Ashby
Parcel 053-20-01109