Back to the backflow review queue

Backflow assembly test: Golden Bakery

Approved

Filed Apr 7, 2024 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 7, 2024
Assembly type
RP
Serial number
B709489
Size
1 1/2
Test gauge serial
G-8561
Gauge calibration date
Jun 16, 2023
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-69-01216
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2366 Meadow Lark Way
Owner: Brandt Holdings LLC
Parcel 053-69-01216