Back to the backflow review queue

Backflow assembly test: Golden Bakery

Approved

Filed May 15, 2025 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 15, 2025
Assembly type
RP
Serial number
B709489
Size
1 1/2
Test gauge serial
G-1193
Gauge calibration date
Dec 18, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-69-01216
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2366 Meadow Lark Way
Owner: Brandt Holdings LLC
Parcel 053-69-01216