Back to the backflow review queue
Backflow assembly test: Golden Bakery
ApprovedFiled Jun 12, 2026 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 12, 2026
- Assembly type
- RP
- Serial number
- B709489
- Size
- 1 1/2
- Test gauge serial
- G-2901
- Gauge calibration date
- Mar 8, 2026
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 1.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Benton, current on the service date
- All required fields present
- Address matches parcel 053-69-01216
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2366 Meadow Lark Way
Owner: Brandt Holdings LLC
Parcel 053-69-01216