Backflow assembly test: 2085 Meadow Lark Ln
Needs reviewFiled Nov 18, 2026 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 18, 2026
- Assembly type
- RP
- Serial number
- Z934167
- Size
- 3/4
- Test gauge serial
- G-4448
- Gauge calibration date
- Aug 15, 2025
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3 psid
- Relief valve opened at
- 4.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Kessler, current on the service date
- All required fields present
- Address matches parcel 053-62-01018
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
2085 Meadow Lark Ln
Owner: Sam Pruitt
Parcel 053-62-01018