Back to the backflow review queue

Backflow assembly test: 8293 Ridgeview Way

Approved

Filed Feb 22, 2025 by Cameron Kessler, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Feb 22, 2025
Assembly type
RP
Serial number
K507876
Size
3/4
Test gauge serial
G-4394
Gauge calibration date
Jun 7, 2024
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-68-01015
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8293 Ridgeview Way
Owner: Logan Danner
Parcel 053-68-01015