Back to the backflow review queue

Backflow assembly test: 4287 Laurel Trl

Sent back

Filed Nov 25, 2026 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 25, 2026
Assembly type
DC
Serial number
Z499472
Size
1
Test gauge serial
G-9337
Gauge calibration date
Sep 12, 2026
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 053-88-01289
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Sent back Please add the test gauge calibration certificate.

Property

4287 Laurel Trl
Owner: Blake Marsh
Parcel 053-88-01289