Back to the backflow review queue
Backflow assembly test: 4287 Laurel Trl
Sent backFiled Nov 25, 2026 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 25, 2026
- Assembly type
- DC
- Serial number
- Z499472
- Size
- 1
- Test gauge serial
- G-9337
- Gauge calibration date
- Sep 12, 2026
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 053-88-01289
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Sent back Please add the test gauge calibration certificate.
Property
4287 Laurel Trl
Owner: Blake Marsh
Parcel 053-88-01289