Back to the backflow review queue
Backflow assembly test: 4384 Spring Branch Trl
ApprovedFiled Sep 11, 2025 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 11, 2025
- Assembly type
- RP
- Serial number
- A103391
- Size
- 3/4
- Test gauge serial
- G-4537
- Gauge calibration date
- May 2, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Pruitt, current on the service date
- All required fields present
- Address matches parcel 053-83-01062
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
4384 Spring Branch Trl
Owner: Rowan Hollins
Parcel 053-83-01062