Backflow assembly test: Riverside Pizza
ApprovedFiled Aug 29, 2024 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 29, 2024
- Assembly type
- DC
- Serial number
- K767627
- Size
- 4
- Test gauge serial
- G-4996
- Gauge calibration date
- Dec 15, 2023
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Pruitt, current on the service date
- All required fields present
- Address matches parcel 053-50-01208
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.