Back to the backflow review queue

Backflow assembly test: Riverside Pizza

Approved

Filed Aug 29, 2024 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 29, 2024
Assembly type
DC
Serial number
K767627
Size
4
Test gauge serial
G-4996
Gauge calibration date
Dec 15, 2023
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 053-50-01208
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4864 Sycamore Rd
Owner: Vance Holdings LLC
Parcel 053-50-01208