Backflow assembly test: Golden Medical Offices

Approved

Filed Aug 3, 2025 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 3, 2025
Assembly type
RP
Serial number
B351298
Size
2
Test gauge serial
G-6923
Gauge calibration date
Jan 26, 2025
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 053-37-01241
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5564 Ridgeview Ct
Owner: Ashby Holdings LLC
Parcel 053-37-01241