Backflow assembly test: Golden Medical Offices

Approved

Filed Aug 27, 2026 by Emerson Hollins, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 27, 2026
Assembly type
RP
Serial number
B351298
Size
2
Test gauge serial
G-3006
Gauge calibration date
Feb 8, 2026
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Hollins, current on the service date
  • All required fields present
  • Address matches parcel 053-37-01241
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5564 Ridgeview Ct
Owner: Ashby Holdings LLC
Parcel 053-37-01241