Backflow assembly test: 5213 Old Church Rd
ApprovedFiled May 28, 2025 by Emerson Hollins, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- May 28, 2025
- Assembly type
- RP
- Serial number
- W274129
- Size
- 3/4
- Test gauge serial
- G-5570
- Gauge calibration date
- Dec 22, 2024
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Hollins, current on the service date
- All required fields present
- Address matches parcel 053-32-01122
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.