Backflow assembly test: 5213 Old Church Rd
ApprovedFiled Jul 4, 2026 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 4, 2026
- Assembly type
- RP
- Serial number
- W274129
- Size
- 3/4
- Test gauge serial
- G-5909
- Gauge calibration date
- Nov 4, 2025
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Hollins, current on the service date
- All required fields present
- Address matches parcel 053-32-01122
- Readings in range, no flags
- Result: passing. Next due date resets when approved.