Back to the backflow review queue

Backflow assembly test: 8033 Hickory Ln

Approved

Filed Dec 20, 2025 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 20, 2025
Assembly type
DC
Serial number
K524655
Size
3/4
Test gauge serial
G-1060
Gauge calibration date
Mar 2, 2025
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-76-01310
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8033 Hickory Ln
Owner: Reese Lindqvist
Parcel 053-76-01310