Backflow assembly test: 5020 Pine Knoll Dr
ApprovedFiled Apr 29, 2026 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 29, 2026
- Assembly type
- RP
- Serial number
- A583444
- Size
- 1
- Test gauge serial
- G-6213
- Gauge calibration date
- Mar 16, 2026
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Kessler, current on the service date
- All required fields present
- Address matches parcel 053-81-01101
- Readings in range, no flags
- Result: passing. Next due date resets when approved.