Backflow assembly test: 5798 Stone Gate Way
ApprovedFiled Dec 18, 2024 by Cameron Ellery, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Dec 18, 2024
- Assembly type
- PVB
- Serial number
- K647793
- Size
- 3/4
- Test gauge serial
- G-5218
- Gauge calibration date
- Mar 18, 2024
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Ellery, current on the service date
- All required fields present
- Address matches parcel 055-64-01312
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.