Backflow assembly test: Crossroads Grill

Approved

Filed Nov 3, 2026 by Parker Brandt, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 3, 2026
Assembly type
RP
Serial number
Z998279
Size
1 1/2
Test gauge serial
G-5753
Gauge calibration date
Jul 20, 2026
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Brandt, current on the service date
  • All required fields present
  • Address matches parcel 055-64-01131
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.