Backflow assembly test: 1194 Ridgeview Trl

Approved

Filed Nov 15, 2026 by Hayden Pruitt, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 15, 2026
Assembly type
RP
Serial number
W801296
Size
1
Test gauge serial
G-6866
Gauge calibration date
Apr 11, 2026
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 055-32-01147
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.