Backflow assembly test: 7597 Pine Knoll Ln

Approved

Filed Oct 15, 2025 by Parker Brandt, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 15, 2025
Assembly type
DC
Serial number
A261728
Size
1
Test gauge serial
G-1474
Gauge calibration date
Aug 6, 2024
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Brandt, current on the service date
  • All required fields present
  • Address matches parcel 055-85-01298
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.