Backflow assembly test: 7180 Turkey Hill Ct

Approved

Filed Sep 17, 2026 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 17, 2026
Assembly type
PVB
Serial number
B491049
Size
3/4
Test gauge serial
G-7265
Gauge calibration date
Jun 25, 2025
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
2.6 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-70-01344
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.