Backflow assembly test: Main Street Self Storage
ApprovedFiled May 18, 2023 by Parker Brandt, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 18, 2023
- Assembly type
- RP
- Serial number
- Z361334
- Size
- 2
- Test gauge serial
- G-3796
- Gauge calibration date
- Nov 16, 2022
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Brandt, current on the service date
- All required fields present
- Address matches parcel 055-79-01267
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3107 Laurel Ln
Owner: Wexler Holdings LLC
Parcel 055-79-01267