ApprovedFiled Jun 16, 2024 by Hayden Fairley, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 16, 2024
- Assembly type
- RP
- Serial number
- Z361334
- Size
- 2
- Test gauge serial
- G-9718
- Gauge calibration date
- Apr 9, 2024
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Fairley, current on the service date
- All required fields present
- Address matches parcel 055-79-01267
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.