Backflow assembly test: Maple Leaf Animal Hospital

Approved

Filed Oct 19, 2025 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 19, 2025
Assembly type
RP
Serial number
B165067
Size
4
Test gauge serial
G-4122
Gauge calibration date
May 18, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-67-01315
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1087 Sycamore Way
Owner: Nguyen Holdings LLC
Parcel 055-67-01315