Back to the backflow review queue
Backflow assembly test: Maple Leaf Animal Hospital
ApprovedFiled Oct 19, 2025 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 19, 2025
- Assembly type
- RP
- Serial number
- B165067
- Size
- 4
- Test gauge serial
- G-4122
- Gauge calibration date
- May 18, 2025
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Calloway, current on the service date
- All required fields present
- Address matches parcel 055-67-01315
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1087 Sycamore Way
Owner: Nguyen Holdings LLC
Parcel 055-67-01315