Backflow assembly test: Maple Leaf Animal Hospital

Filed Nov 20, 2026 by Parker Brandt, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 20, 2026
Assembly type
RP
Serial number
B165067
Size
4
Test gauge serial
G-2206
Gauge calibration date
Sep 8, 2026
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Brandt, current on the service date
  • All required fields present
  • Address matches parcel 055-67-01315
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

1087 Sycamore Way
Owner: Nguyen Holdings LLC
Parcel 055-67-01315