Back to the backflow review queue

Backflow assembly test: 6929 Hickory Ln

Approved

Filed Oct 27, 2025 by Alex Okafor, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 27, 2025
Assembly type
PVB
Serial number
A463915
Size
3/4
Test gauge serial
G-8532
Gauge calibration date
Jan 23, 2025
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Okafor, current on the service date
  • All required fields present
  • Address matches parcel 055-39-01352
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6929 Hickory Ln
Owner: Reese Danner
Parcel 055-39-01352