ApprovedFiled Feb 26, 2025 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 26, 2025
- Assembly type
- RP
- Serial number
- B579787
- Size
- 1
- Test gauge serial
- G-6563
- Gauge calibration date
- Sep 4, 2024
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Calloway, current on the service date
- All required fields present
- Address matches parcel 055-38-01327
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.