Backflow assembly test: Hilltop Brewing Co
ApprovedFiled Feb 15, 2026 by Cameron Ellery, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 15, 2026
- Assembly type
- RP
- Serial number
- A948072
- Size
- 4
- Test gauge serial
- G-1772
- Gauge calibration date
- Sep 2, 2025
- Check valve 1
- 6.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Ellery, current on the service date
- All required fields present
- Address matches parcel 055-50-01341
- Readings in range, no flags
- Result: passing. Next due date resets when approved.