Back to the backflow review queue

Backflow assembly test: 798 Quarry Rd

Approved

Filed May 18, 2025 by Parker Brandt, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
May 18, 2025
Assembly type
RP
Serial number
A136386
Size
3/4
Test gauge serial
G-6823
Gauge calibration date
Jan 13, 2025
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Brandt, current on the service date
  • All required fields present
  • Address matches parcel 055-90-01199
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

798 Quarry Rd
Owner: Riley Marsh
Parcel 055-90-01199